sales contact:
E-mail: info@senoparts.com
Tel: +86 15005572679
Add: Jingying E-commerce Industrial Park, No.678 Huaxi Road,Wucheng District, Jinhua City, Zhejiang Province, China
Smartgen HPD200 Reverse Power Protection Module
HPD200 is a reverse power protection module, which used to monitor active power of marine generator. It can offer reverse power protection for parallel and grid connection of marine and land genset.
PERFORMANCE AND CHARACTERISTICS
1.Can accurately detect reverse power of generator, offering timely protection.
2.Power indication, reverse power indication and output status indication.
3.Normally open/close passive contact output.
4.Reverse power threshold and output delay can be adjusted.
5.Modular design, compact structure, small volume, light weight and easy installation.
6.Guide rail mounting or fixed by crews.
PARAMETER DEFINITION AND RANGE
1.Rated voltage and frequency input: 3 phase AC 380V±20%, 50Hz/60Hz
2.Rated current input: 5A
3.Setting range of reverse power protection: 1%~20%
4.Time of reverse power protection: (1~6)s
5.Power consumption: when module is under rated voltage, power
consumption of voltage circuit is not more than 1.5VA; when module is
under rated current, power consumption of current loop is not more than
1VA.
6.Capacity of output contact: AC, 250V, 7A