Smartgen HGM190HC Genset Controller
The
Model HGM190hc is an Automatic Engine Control Module. The module is
used to automatically start and stop the engine, indicating the
operational status and fault conditions, automatically shutting down the
engine and indicating the engine failure by LED on the front panel.
Operation
If
you use hgm190 for the first time, configure is necessary. If you want
to configure the module, please look Configuration.Operation of the
module is via a three position key switch mounted on the front panel
with OFF (O), START and AUTO positions. In the ‘O’ position the output
are de-energized.
Manual Operation:
1. Select manual run
2. Depress pre-heat button for required length of time
3. Press START to crank engine
Once
the Start button is pressed and maintained, the engine fuel system is
energized. The ‘Crank’ output is then energized and the starter motor
operated, disengaging automatically when the engine fires or when the
‘Start’ button is released. The protection hold-off timer is then
initiated.
Automatic Operation:
1. Select AUTO
2. When Remote Start is active, the generator will automatic start.
Operation of any of the following alarms (which are close on fault) will cause the run output to de-energize:
. Low Oil Pressure
. High Engine Temperature
. Auxiliary Shutdown
. Over speed
This
will remove the fuel supply from the engine and bring it to rest. Each
alarm has its own LED indicator and once activated no further alarm
conditions will be accepted. The alarm output and relevant LED will
remain active until the unit is reset by turning the switch to the ‘O’
position.
Over speed Protection
Over speed protection is derived
from magnetic pickup sensor. Over 114% of rated speed will shutdown the
engine. During engine cranking and for a short time afterwards the
protection hold-off timer (10 seconds) is active and the relevant alarm
inputs are inhibited. This enables the engine to start and achieve
normal running conditions. Once the timer has expired the inputs are
enabled providing normal protection from the module.
Charge Failure warning
Charge
Failure warning is also provided by monitoring the WL terminal on the
charge alternator. This operates on a similar principal to the warning
lamp fitted in a motor vehicle, should the output fail the charge fail
LED will illuminate. The module will also provide the alternator
excitation current via this connection.
Specification
DC Supply: 8 to 35 V Continuous.
Speed Sensor Input Range: 1 – 70V(p-p)
Speed Sensor Input Frequency: 500Hz -10KHz.
Start Output: Relay 16 Amp DC at supply voltage.
Fuel Output: Relay 16 Amp DC at supply voltage.
Pre-heat Output: Relay 16 Amp DC at supply voltage.
Stop Output: Relay 16 Amp DC at supply voltage.
Configure
Output: Relay 16 Amp DC at supply voltage.This output can configure
Alarm output or Idle output by the code switch on the under side.
Operating Temperature Range: -30 to +70°C