sales contact:
E-mail: info@senoparts.com
Tel: +86 15005572679
Add: Jingying E-commerce Industrial Park, No.678 Huaxi Road,Wucheng District, Jinhua City, Zhejiang Province, China
Kutai GCU-20 Generator Set Control Unit
GCU-20
Automatic Engine & Generator Control Unit has many useful functions
like annunciator alarm output and selectable EM81 / EM121 MPU signal
for speed sensing. It's suitable for pump engine control. GCU-20 also
provide IDLE control for electronic governors.
*Together with RA-20 Annunciator Module to help user monitor onsite and remote monitoring and warning.
Features
Microprocessor Based Design
Universal LED Graphic Interface, Displays Generator Status and Failures
Modular Design, Quick Installation
With Annunciator Alarm Output
Selectable MPU Signal for Speed Sensing
Suitable for Pump Engine control
With Lamp Test Function for All Front Panel LEDs and Annunciator Lamps
Provide IDLE control For Elec. Governors
Five Adjustable Time Delay Potentiometers
Six DIP Switches For Setting Different Engine Parameters
Specifications
DCSupply | Voltage9to36VDC |
AlternatorInputRange | Voltage5~300VAC |
Frequency50/60Hz | |
MPUSignalInputRange | ±2Vto70VPeak |
RatedMPUFrequency | 100Hz~10,000Hz |
FuelSolenoidSignalOutput | 10Amp@12/24VDC |
StartSignalOutput | 10Amp@12/24VDC |
AnnunciatorOutput | 300mA@12/24VDC |
PowerConsumption | Under3watt |
Protection&AlarmStatusIndicators | StartFailure |
HighWaterTemp. | |
LowOilPressure | |
NoSpeedSignal | |
Overspeed | |
Underspeed | |
ExtraProg.Input | |
AdjustableTimers | EnginePre-Heat:2~30Seconds |
StarterCrankingTime:1~15Seconds | |
EnergizetoSTOP:1~15Seconds | |
EngineIdle(Governor):0~300Seconds | |
ngineCool-Down:0~300Seconds | |
Environment | OperatingTemperature:-20~70°C |
StorageTemperature:-35~85°C | |
RelativeHumidity:Maximum90% | |
Dimensions | 88.0(L)x88.0(W)x37.5(H)mm |
Weight | 206g±2% |