Smartgen HAT530N ATS Controller

Smartgen HAT530N ATS Controller
Smartgen HAT530N ATS Controller
Smartgen HAT530N ATS Controller
Smartgen HAT530N ATS Controller
Smartgen HAT530N ATS Controller
Product Name : Smartgen HAT530N ATS Controller
Product ID : HAT530N
MOQ : 1pc
Packaging : Individual packing or neutral packing
Delivery time : about 3 working days
Payment terms : T/T,West Union,Paypal
Supply ability : 3000pcs/month
Introduction

Smartgen HAT530N ATS Controller

 

The powerful Microprocessor contained within the HAT530 ATS controller allows for precision voltage(2-way 3-phase/single phase) measuring and make accurate judgment on abnormal voltage (power lost, over/under voltage, over/under frequency, loss of phase, phase sequence wrong) and control ATS to tranfer after the delay has expired. This controller is suitable for NO Breaking ATS. When 1# is abnormal, the controller will send signal to start genset after the "1# abnormal delay" has expired. "Three remote"(remote control, remote measurement and remote communication) function can be implemented with the help of LINK communication port.

PERFORMANCE AND CHARACTERISTICS

HAT530 ATS controller can monitor 2-way 3-phase 4-wire voltage, 2-phase 3-wire and single-phase 2-wire voltage (2 way mains, or 1 way mains and 1 way generator) and control ATS to transfer. Its performance and characteristics are shown as below,

1.Measure and display 2-way 3 phase Voltage and Frequency;
2.Over/under voltage, loss of phase, phase sequence wrong, over/under frequency protection function. As default, phase sequence wrong protection and over/under frequency protection are disable; however, users can set the protection function as need.
3.Parameters can be set via PC software using SG72 module (USB to LINK) or other converse module.
4.The voltage normal delay of 1# or 2#can be set in (0~60) seconds and the Genset start delay can be set in (0~3600) seconds.
5.The voltage abnormal delay of 1# or 2#can be set in (0~60) seconds and the Genset stop delay can be set in (0~3600) seconds.
6.“1# power priority”, “Auto/Manual”, “No priority” and “2#power priority” can be set via controller front panel.
7.Closing output signal can be set as on intervals or as continuous output.
8.Applicable for 2 isolated neutral line.
9.Auto/Manual mode. In manual mode, ATS transfer can be implemented via panel pushbutton.
10.Forced Open input port; When the input port is active, the switch will be Breaking position forcedly (woks for the ATS with Breaking Position).
11.AUX.OUTPUT 1 and AUX.OUTPUT 2 can be configured to make it easy to transfer power supply.
12.LEDs mounted on front panel can clearly show ATS running status.
13.The output contactor capacity of 1# and 2#power supply transfer relay (1#CLOSE, 2#CLOSE) is 5A AC250V, volts-free contact, can be directly used in driving switch to transfer.
14.The output contactor capacity of Genset start relay (GENS START) is 7A AC250V/7A DC28V, volts-free N/C contact.
15.Suitable for various AC systems (3 phase 4-wires, 2-phase 3-wires and single-phase 2-wire).
16.Controller has strong ability of anti-electromagnetic interference, can be used under complex electromagnetic interference environment.
17.Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,compact structure with easy installation.

SPECIFICATION

Items

Contents

Operating Voltage

AC170V~277V during AC power L1N1/L2N2 supply.

Power Consumption

<3W (Standby mode: <1W)

AC Voltage Input

3P4W (ph-N)

1P2W (ph-N)

2P3W (ph-N)

 

AC170V~AC277V(ph-N)

AC170V~AC277V (ph-N)

AC170V~AC277V(ph-N)

Rated Frequency

50/60Hz

1# Close Relay Output 

5A  AC250V  Volts free output

2# Close Relay Output 

5A  AC250V  Volts free output

Open Relay Output

5A  AC250V  Volts free output

AUX.OUTPUT 1

16A  AC250V  Volts free output

AUX.OUTPUT 2

16A  AC250V  Volts free output

Gen Start Relay

7A  AC250V  Volts free output

1# Close Input

COM2 connect is active.

2# Close Input

COM2 connect is active.

Forced Open Input

COM2 connect is active.

Communication

LINK interface, MODBUS Protocol

Case Dimensions

139mmx120mmx48mm

Panel Cutout

130mmx111mm

Working Conditions

Temperature: (-25~+70)°C;   

Humidity: (20~93)%RH

Storage Condition

Temperature: (-25~+70)°C

Protection Level

IP55 Gasket 

Insulation Strength

Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;

The leakage current is not more than 3mA within 1min.

Weight

0.51kg

 

 

Inquiry
If you have any interests in the product,just feel free to contact us online or by email.Thank you.
Title:
 
Your name:
 *
Email:
 *
Telephone:
 
Message:
 *
Code:
   *
     Items marked with * have to be filled in